Barrier Cable Glands for All Types of Armoured Cables
Mining, Gas, Dust applications
Ex I M2 – Ex db IMb Ex eb IMb

CERTIFICATES

Delivery and return
Delivery and return
Shipping Information
Shipping Information
Composition and care
Composition and care

Description

Suitable for use in Group I, Group II, Group III
Equipment Marking EX I M2 Ex db I Mb, Ex eb I Mb
EX II 2GD Ex db IIC Gb, Ex eb IIC Gb, Ex tb IIIC Db
Ingress Protection Rating IP66, IP68 – 5 Bar, 30 min
Type Rating TYPE 4X
Cable Gland Material Brass, Brass Nickel Plated, Stainless Steel
Seal Material Silicone
Operating Temperature Silicone: -60°C to +100°C
Thread Type Metric, NPT
Other thread types available upon request.
Cable Type Armoured (SWA, AWA, STA), Braided, Shielded
Accessories Lock nuts, Gaskets (Washers), Serrated Washers, Shrouds, Earth tags
Remarks Accessories must be ordered separately.
O-ring available in Metric outer threads.
Product Certificates
ATEX Approval CESI 17 ATEX 007X
ATEX standards EN 60079-0, 1, 7, 31
IECEx Approval IECEx CES 17.0029X
IECEx standards IEC 60079-0, 1, 7, 31
TR CU (EAC) No TC RU C-TR.AA87.B.00941
TR CU standards ГОСТ 31610.0; ГОСТ IEC 60079-1, 7, 31
Marine Approval TAE00003WU
UKCA CML 22UKEX1185X

Technical

Product Selection Table
Showing:
Thread Type METRIC acc. to ISO 965-3

Outer Thread Size
(Male)
Clamping Range

Ø min – max mm

Over Conductors

Ø max mm

Armour Wire

Ø max mm

Outer Thread Length

TL
mm

Spanner Width
Outer Ø
D
mm

max. Height
H
mm
 

Part Number

Needed Barrier Compound Mixture
Per Pcs.
(g)
Cap

SW Cap mm

Upper Body

SW Upper Body
mm

Lower Body

SW Lower Body
mm

M20x1,5 3,0 – 8,5 9,5 1,0 16,0 25 25 25 27,0 63,5 KBCTA1XSM 7
6,0 -13,0 9,5 1,3 16,0 25 25 25 27,0 63,5 KBCTA1SM 7
8,0 – 15,0 9,5 1,3 16,0 25 25 25 27,0 63,5 KBCTA1M 7
13,5 – 21,0 12,0 1,3 16,0 30 30 30 33,0 65,0 KBCTA1LM 9
M25x1,5 8,0 – 15,0 9,5 1,3 16,0 25 25 30 33,0 63,5 KBCTA2SM 7
13,5 – 21,0 12,0 1,3 16,0 30 30 30 33,0 65,0 KBCTA2M 9
18,0 – 27,0 15,0 1,6 16,0 40 40 40 44,5 72,5 KBCTA2LM 20
M32x1,5 18,0 – 27,0 15,0 1,6 16,0 40 40 40 44,5 72,5 KBCTA3M 20
23,0 – 33,0 21,5 1,6 16,0 43 43 43 47,0 74,5 KBCTA3LM 31
M40x1,5 23,0 – 33,0 21,5 1,6 16,0 43 43 45 50,0 74,5 KBCTA4SM 31
29,0 – 40,0 29,0 2,0 16,0 50 50 50 55,5 82,5 KBCTA4M 60
M50x1,5 29,0 – 40,0 29,0 2,0 16,0 50 50 55 61,0 82,5 KBCTA5SM 60
35,0 – 48,0 37,0 2,5 16,0 58 58 58 64,0 90,5 KBCTA5M 90
M63x1,5 35,0 – 48,0 37,0 2,5 20,0 58 58 68 75,0 90,5 KBCTA6SM 90
42,0 – 56,0 46,0 2,5 20,0 75 75 75 83,0 120,0 KBCTA6M 193
M75x1,5 42,0 – 56,0 46,0 2,5 20,0 75 75 80 89,0 120,0 KBCTA7SM 193
54,0 – 70,0 58,0 3,2 20,0 100 100 100 110,5 126,0 KBCTA7M 337
M90x1,5 54,0 – 70,0 58,0 3,2 20,0 100 100 100 110,5 126,0 KBCTA8M 337
Thread Type NPT acc. to ANSI ASME B1.20.1
Outer Thread Size
(Male)
Clamping Range

Ø min – max mm

Over Conductors

Ø max mm

Armour Wire

Ø max mm

Outer Thread Length

TL
mm

Spanner Width Outer Ø

D
mm

max. Height

H
mm

 

Part Number

Needed Barrier Compound Mixture
Per Pcs. (g)
Cap

SW Cap mm

Upper Body

SW Upper Body
mm

Lower Body

SW Lower Body
mm

NPT 1/2″ 3,0 – 8,5 9,5 1,0 21,0 25 25 25 27,0 63,5 KBCTA1XSN 7
6,0 – 13,0 9,5 1,3 21,0 25 25 25 27,0 63,5 KBCTA1SN 7
8,0 – 15,0 9,5 1,3 21,0 25 25 25 27,0 63,5 KBCTA1N 7
13,5 – 21,0 12,0 1,3 21,0 30 30 30 33,0 65,0 KBCTA1LN 9
NPT 3/4″ 8,0 – 15,0 9,5 1,3 21,0 25 25 30 33,0 63,5 KBCTA2SN 7
13,5 – 21,0 12,0 1,3 21,0 30 30 30 33,0 65,0 KBCTA2N 9
18,0 – 27,0 15,0 1,6 21,0 40 40 40 44,5 72,5 KBCTA2LN 20
NPT 1″ 18,0 – 27,0 15,0 1,6 26,0 40 40 40 44,5 72,5 KBCTA3N 20
23,0 – 33,0 21,5 1,6 26,0 43 43 43 47,0 74,5 KBCTA3LN 31
NPT 1 1/4″ 23,0 – 33,0 21,5 1,6 28,0 43 43 45 50,0 74,5 KBCTA4SN 31
29,0 – 40,0 29,0 2,0 28,0 50 50 50 55,5 82,5 KBCTA4N 60
NPT 1 1/2″ 29,0 – 40,0 29,0 2,0 28,0 50 50 55 61,0 82,5 KBCTA5N 60
NPT 2″ 35,0 – 48,0 37,0 2,5 28,0 58 58 65 72,0 90,5 KBCTA6N 90
NPT 2 1/2″ 42,0 – 56,0 46,0 2,5 41,0 75 75 80 89,0 120,0 KBCTA7N 193
NPT 3″ 54,0 – 70,0 58,0 3,2 43,0 100 100 100 110,5 126,0 KBCTA8N 337
*Barrier compound is served as 50 g standard.